1. 3 phase input, 3 phase output pure online dual conversion products, support 380 / 400 / 415V, 50 / 60Hz power grid system, to provide the best power quality and load protection.
2. Super load adaptability, super overload and short circuit capacity.
3. Ultra-wide input voltage and frequency range, adapt to the harsh power grid environment, adapt to the use of various fuel generators.
4. The input power factor is up to 0.99, the input harmonic current is less than 3%, and the overall efficiency is greater than 95%. Green, high efficiency and energy saving.
5. DSP full digital control realizes full digital control of power conversion links such as rectification, inversion and charge and discharge.
6. Digital cycle control technology, high reliability.
7. Intelligent battery management scheme to prolong the battery life.
8. The system adopts a modular design, with a stable and reliable performance.
9. All the fans in the system are redundant in design, which greatly improves the reliability of the system.
10.The EPO emergency shutdown function can be realized.
11.Ultra-long average failure-free time (>200,000 hours) and ultra-low average maintenance time (<0.5 hours).
12.Rich accessories: dust net, SNMP network communication card, lightning protection module, battery temperature compensator, mobile phone SMS alarm.
13.All circuit boards adopt three-proof technology.
14.Traditional modular UPS can be replaced by parallel, saving the high cost of modular cabinet.
15.7-inch real color touch screen (rack type LCD display) enables users to more intuitively understand the working state and operating parameters of UPS, such as input and output voltage and frequency, load size, battery capacity, machine temperature, etc., so that all operations are clear at a glance.
Capacity | 20/30/40kVA | 60/80kVA | 100/120kVA | 150/180kVA |
Import | Input mode | Three-phase, four-wire+grounding |
Rated voltage | 380/400/415Vac |
Voltage range | 138 to 485Vac; 305 to 485Vac, 138 to 305 Vac |
Frequency range | 40~70Hz |
Power factor | ≥0.99 |
Input current harmonics | 3% (100% nonlinear load) |
Bypass range | Upper limit of bypass protection voltage: 220V: +25% (optional +10%, +15%, +20%); 230V: +20% (optional +10%, +15%); 240V: +15% (optional +10%) |
Lower pass protection voltage limit: -45% (optional-10%, -20%, -30%) |
Bypass frequency protection range: ±10% |
Output | Output method | Three-phase, four-wire+grounding |
Rated voltage | 380/400/415Vac |
Power factor | 0.9 |
Voltage accuracy | ±1% |
Output frequency | Main mode | Synchronized with input; output frequency 50 (1±0.02%) Hz beyond ±10% (±1%, ±2%, ±4%, ±5%) |
Battery mode | (50/60±0.2%)Hz |
Load peak ratio | 3:1 |
Output voltage distortion | 2% linear load, and 4% nonlinear load |
Battery | Battery voltage | Voltage optional: ±180V/±192V/±204V/±216V/±228V/±240V/±252V/±264V/±276V/±288V/±300V (30/32/34/36/38/40/42/44/46/48/50) 360Vdc~600Vdc(30~50sections optional) |
Charging current | 15A max | 15A max | 30A max | 45A max |
Transfer time | Municipal mode to bypass mode: 0ms (tracking); municipal mode to battery mode: 0ms |
Protect | Overload capacity | Load ≤110%, 60mins;≤125%, 10mins; ≤150%, 1min; >150%, shutdown immediately. |
Overtemperature protection | Normal mode: Switch to the bypass mode; Battery mode: Turn off the output immediately |
Emergency Shutdown (EPO) | Cut off the output immediately |
Communication interface | USB, RS485, optical coupling node, machine (option), SNMP card (option), Relay card (option) |
Work environment | Working temperature | 0℃~40℃ |
Relative humidity | 0~95% with no condensation |
Storage temperature | -25℃~55℃ |
Altitude | <1500m, exceed 1500m according to GB/T 3859.2 |
Physical characteristics | Dimensions (D×W×H) | 730×250×530mm(rack type 443×131×580mm) | 850×250×860mm | 850×440×1200mm |
Net weight (Kg) | 45/45.5/45.8 | 73/75 | 140/149 | 190/199 |
Operative standard | YD/T1095-2018 |
* The above parameters may be adjusted and changed, please refer to the physical object.